Search

What power factor are generator ratings based on?

What size generator do I need for my home? Why do two sets with the same kVA run different loads? How do I turn a kVA rating into the kW my appliances actually use?

A generator's kVA rating, its power factor, and the kW it can truly deliver are all set out in plain terms, so you can match a set to your fridge, freezer, boiler and lights before you buy.

A small portable petrol generator sits on a garage floor beside a blank datasheet, a calculator and a plug-in heater and fridge magnet-free appliance lead arrangement, suggesting a household buyer checking a rating before purchase.
In this answer
  1. Power Factor Meaning
  2. Why Ratings Use 0.8 Power Factor
  3. kVA versus kW
  4. Convert Rating to Load
  5. Single-Phase versus Three-Phase
  6. Load Power Factor Below Rating

Short answer

A generator's rating is quoted in kVA, apparent power, at a conventional power factor of 0.8. The usable real power in kW is therefore 80% of the kVA figure. A set sold as 10 kVA delivers roughly 8 kW to a load at that reference power factor. Which? states the relationship plainly: "the kW (the usable power) will be less than this, 80% of the kVA"1.

That single convention explains most of the confusion around generator sizing. Two generators of the same physical size can carry different labels depending on whether the maker quotes kVA or kW, and a household adding up appliance wattages in kW is working in a different unit from the one on the sales sheet. The conversion is not difficult, but it has to be done before a set is chosen, not after.

This page sets out what power factor means for a rating, why 0.8 is the reference, how to move between kVA and kW, and where single-phase household supplies differ from three-phase. It also covers what happens when the load's power factor is lower than the rating assumes, which is the case that catches buyers out.

What power factor means for a generator rating

Power factor is the ratio between real power, measured in kW, and apparent power, measured in kVA. Real power does the work: it turns a motor, heats an element, lights a room. Apparent power is the product of voltage and current flowing in the circuit, and it is always at least as large as the real power because alternating current in inductive loads such as motors and transformers is out of step with the voltage.

A generator has two limits that matter. Its alternator and windings are limited by current, which is an apparent power limit expressed in kVA. Its engine is limited by the mechanical power it can deliver, which is a real power limit expressed in kW. The rating label ties the two together at a stated power factor. When a maker quotes a single figure in kVA, the kW available depends on the power factor of whatever is plugged in.

For a household, this matters because the loads are mixed. A resistive heater draws current in step with voltage and sits close to unity power factor. A fridge compressor, a circulating pump or a heat pump does not. The Energy Saving Trust notes that for domestic wind generation "the stronger the wind, the more energy produced", and Home Energy Scotland makes the same point for hydro: "the greater the height and the more water there is flowing through the turbine, the more electricity generated"5. Those are statements about output, but they underline that generation is rated against conditions, and power factor is one of the conditions a generator rating assumes.

The practical consequence is that a generator's kVA figure is not a promise of kW. It is a promise of current capacity at a stated power factor, and the kW follows from what the load does with it.

Why ratings are quoted at 0.8 power factor

A portable petrol generator with wheels standing on a grassy field
A portable petrol generator standing outdoors Image: BLUETTI

The 0.8 figure is a convention, not a measurement of any particular house. It represents a mixed commercial or industrial load where motors, transformers and electronics pull the power factor below unity, and it has been used for so long that it functions as a standard reference point across the generator market.

Rating at 0.8 does two things. It gives a conservative kW figure that most real loads will not exceed, and it gives a common basis for comparing sets from different makers. A generator rated 10 kVA at 0.8 is understood to deliver 8 kW, and a buyer comparing it with a set rated 8 kW can see they are broadly the same machine.

The convention is not universal across all equipment. A Bluegen unit measured 0.9992 at full output, close to unity7. These are inverters and generators of a different kind, but they show that 0.8 is a rating convention rather than a physical constant.

For a household buying a petrol or diesel set, the 0.8 convention is the one that applies. It is worth checking whether a maker quotes a kW figure derived at 0.8 or a standalone kW rating, because the two are not the same claim.

Apparent power (kVA) versus real power (kW)

The distinction between kVA and kW is the whole subject in one line. Apparent power is what the alternator must be able to carry. Real power is what the engine must be able to drive and what the appliances actually consume.

The two are linked by the power factor: kW = kVA × power factor. At 0.8, kW is 80% of kVA. At unity, they are equal. Nothing in between is unusual in a house.

QuantityUnitWhat it measuresLimit it imposes
Apparent powerkVAVoltage × current in the circuitAlternator and winding current
Real powerkWPower doing useful workEngine mechanical output
Power factorratioReal power divided by apparent powerRelationship between the two

The Energy Saving Trust's jargon buster defines a gigawatt as "a unit of power equal to 1 billion watts, typically used to describe the output of large power plants or the total electricity"8. That is the scale of the grid. A household generator sits at the other end, and the same unit logic applies: watts, kilowatts and kilovolt-amperes are all measures of power, but they are not interchangeable without the power factor.

For a household, the kVA figure is the one that determines whether the set can carry the current without tripping or overheating. The kW figure is the one that determines whether the engine can turn the load. Both have to be satisfied.

How to convert a generator rating to the power your appliances need

A kitchen corner with a standing fridge, its door closed, connected by a plug and cable to a small portable generator on the floor nearby, with a simplified isometric figure crouching beside the generator checking it as the fridge starts.
A fridge that draws a starting surge

The conversion runs in two directions, and it is worth being clear which one applies.

To go from a generator's kVA rating to the kW it will deliver at 0.8 power factor, take 80% of the kVA. A 10 kVA set gives about 8 kW. To go from a known load in kW to the kVA a connection application needs, NIE Networks gives the factor: "If you know your load information in kW, you can convert it to kVA by multiplying by the factor 1.05: kVA = kW × 1.05"2.

To add up a household load, the Consumer Council's appliance cost checker gives the basic unit conversion: "1000W = 1kW"3. Sum the running watts of everything to be powered, convert to kW, then divide by 0.8 to find the kVA the generator must be rated at.

For reference, Which? lists a Dewalt dual voltage generator at "Power output: 3500W" and an Impax suitcase inverter generator at "Power output: 1900W"1. Those are real examples of the size range a household is choosing between, and both are quoted in watts rather than kVA, which is common for smaller portable sets.

Where single-phase household ratings differ from three-phase

Most UK homes have a single-phase supply. Three-phase is uncommon: Nesta refers to "the 1% of households requiring three-phase connections"10. That single fact shapes the whole comparison, because the rating limits that apply to generation connections differ by phase count.

NIE Networks classes small scale renewable generation as "greater than 3.68kW and up to 17kW single phase and greater than 11.04kW and up to 5MW three phase"11. SP Electricity North West refers to "11.04kW of generation on a three-phase supply, as part of permitted rights"12. SSEN notes that most homes and small businesses can upgrade from single-phase to three-phase, "giving you up to 69kVA"13.

Supply typeGeneration thresholdSource
Single phasegreater than 3.68kW and up to 17kWNIE Networks11
Three phasegreater than 11.04kW and up to 5MWNIE Networks11
Three phase permitted rights11.04kW per propertySP Electricity North West12
Single to three-phase upgradeup to 69kVASSEN13

The phase count also affects how a generator is connected. SSEN requires a schematic drawing showing "the generator itself; name and power rating (kW) of the inverter being used; live phases, neutral, earth; lockable isolators; clear demarcation between our and your equipment"14. The power rating on the inverter type test certificate must match the rating on the schematic14.

For a household on a single-phase supply, the practical ceiling on what can be connected without a full application is low. SSEN states that an application is still required "even if the total generation across all properties or generators is below 3.68kW" in certain circumstances, including multiple properties or multiple generators at one property15. The rules are set out in more detail on the page covering generator grid connection notification.

What happens if your load power factor is lower than the rating

A printed maker's datasheet lying on a workbench beside a small standby generator, its page showing a plain specification block with a highlighted band marking the permitted power factor range, with no readable words or numbers.
The maker's datasheet for the generator

A load with a power factor below 0.8 draws more current for the same real power than the rating assumes. The generator's alternator reaches its current limit before the engine reaches its kW limit, so the set is effectively derated: less real power is available than the kW figure on the label suggests.

This is the case that catches buyers out. The engine has capacity to spare while the alternator is at its ceiling.

The maker's datasheet states the permitted power factor range. The Sungrow inverter datasheet gives "0.8 leading to 0.8 lagging"16, and that range is typical of the specification a generator will carry. Operating outside it can affect voltage regulation and cause overheating.

Fuel consumption tracks real power, not apparent power. Tesla Powerwall guidance states that "a 5kW petrol generator burns 1 to 2 litres per hour, with fuel expenses increasing during outages"4. The same guidance notes that generators "burn petrol, diesel, or LPG, releasing carbon emissions and contributing to air pollution"4. A low power factor load does not increase the fuel burn directly, but it does mean the generator is working closer to its current limit for the same useful output, which raises losses.

For a household, the independence question is straightforward. A generator rated at 0.8 power factor gives a predictable kW figure for a mixed load, and that is what the rating is for. The dependence that remains is on fuel: petrol, diesel or LPG, stored and replenished, with the safety and storage rules that apply. The page on generator fuel and running costs covers that side, and generator safety covers carbon monoxide and earthing.

Sources16 cited
  1. How to buy the best generator, Which?, 2026-01-20
  2. NIE Networks single house connection application, NIE Networks, 2026-09-19
  3. Appliance Cost Checker Tool, Consumer Council, 2026
  4. Powerwall 3 or generator, Tesla Powerwall, 2026-09-17
  5. Generating renewable electricity, Energy Saving Trust, 2025-12-11
  6. Hydroelectricity, Home Energy Scotland, 2026-09-20
  7. Bluegen product type test register, ENA, 2026-09-17
  8. Energy jargon buster, Energy Saving Trust, 2026-03-20
  9. NIE Networks Connections Portal application, NIE Networks, 2026-09-19
  10. 10 things to make getting a heat pump easier, Nesta, 2026-02-12
  11. NIE Networks generation connections FAQs, NIE Networks, 2026-09-19
  12. SP Electricity North West renewable energy installation, SP Electricity North West, 2026-09-19
  13. SSEN supply upgrade FAQs, SSEN, 2026-09-17
  14. SSEN micro-generation connection (50kW or less), SSEN, 2026-09-17
  15. SSEN installations up to 3.68kW per phase at more than one property, SSEN, 2026-09-17
  16. Sungrow SG2.0/2.5/3.0RS-S datasheet, Sungrow, 2026-09-17

Questions

Answers here, and more on their own pages.

Is a generator rating in kW or kVA?

Most generators are sold with a kVA rating, which is apparent power, and a kW rating, which is real power. The kW figure is the usable power and is typically 80% of the kVA figure at a 0.8 power factor. A 10 kVA generator therefore delivers about 8 kW of real power. Some smaller domestic sets are quoted in watts instead.

Why are generators rated at 0.8 power factor?

A 0.8 power factor is a conventional reference point that reflects a mixed load of motors, transformers and electronics, which draw current out of step with voltage. Rating at 0.8 gives a realistic usable kW figure for typical commercial and industrial loads. A purely resistive load such as a heater has a power factor close to 1, so the same generator could deliver more real power to it.

How do I calculate kVA from kW for a generator?

NIE Networks gives the conversion as kVA = kW multiplied by 1.05 for load information on a connection application. That factor reflects a power factor of roughly 0.95 rather than 0.8. For a generator rated at 0.8 power factor, the reverse applies: kW is 80% of kVA, so a 10 kVA set gives about 8 kW.

What power factor do household appliances have?

It varies widely. Resistive loads such as kettles and heaters sit close to unity. Motors in fridges, freezers and pumps have a lower power factor, and electronic devices with switched-mode power supplies can be lower still. A single figure cannot be applied to a whole house, which is why generator ratings use a conventional 0.8 reference rather than a measured household value.

Can I run a generator at unity power factor?

A generator can supply a resistive load at close to unity power factor, and the real power delivered can approach the kVA rating. However, the generator is still rated at 0.8, and sustained operation outside the rated power factor range can affect voltage regulation and heating. The maker's datasheet states the permitted range, which for one inverter is 0.8 leading to 0.8 lagging.

Does power factor affect generator fuel consumption?

Fuel consumption tracks the real power delivered, not the apparent power. A 5kW petrol generator burns 1 to 2 litres per hour according to maker guidance. If a load has a low power factor, the generator must supply more current for the same real power, which increases losses and can push the set towards its current limit before its kW limit is reached.

What size generator do I need for a 0.8 power factor load?

Add up the running watts of the appliances to be powered, convert to kW using 1000W = 1kW, then divide by 0.8 to find the kVA the generator must be rated at. Allow for starting surges from motors. For reference, a Dewalt dual voltage generator is rated at 3500W and an Impax suitcase inverter generator at 1900W.